B-54 Parameters
1503-UM054C-EN-P – June 2013
Type of Contactor Selected for IB4 [IB 4 Contactor Type]
Parameter Number: 96,84,_,_,_.
Access rule: Get
Data Type: USINT
Object Mapping: 0x384-4-14
Group: Configuration
Units : -
Minimum Value: 0
Maximum Value: 3
Default Value: 0
This parameter allows the user to view the status of the type of
contactor that is being controlled by the IB4 module. This value is
set by the DIP switches on the IB4 module only (see Table 8.C).
Table B.21 – Type of Contactor for IB4 Unit
Value Enum Text Description
IB4 is a 400A Mechanically Latched contactor
IB4 is a 400A Electrically Held contactor
IB4 is an 800A Mechanically Latched contactor
IB4 is an 800A Electrically Held contactor
Type of Contactor Selected for IB5 [IB 5 Contactor Type]
Parameter Number: 97,_,_,_,_.
Access rule: Get
Data Type: USINT
Object Mapping: 0x384-5-14
Group: Configuration
Units : -
Minimum Value: 0
Maximum Value: 3
Default Value: 0
This parameter allows the user to view the status of the type of
contactor that is being controlled by the IB5 module. This value is
set by the DIP switches on the IB5 module only (see Table 8.C).
Table B.22 – Type of Contactor for IB5 Unit
Value Enum Text Description
IB5 is a 400A Mechanically Latched contactor
IB5 is a 400A Electrically Held contactor
IB5 is an 800A Mechanically Latched contactor
IB5 is an 800A Electrically Held contactor
Comentarios a estos manuales