Parameters B-25
1503-UM054C-EN-P June 2013
Hold Coil Current for IntelliVAC Base Unit #4
[IB 4 Hold Current]
Parameter Number: 44,36,_,_,_.
Access rule: Get
Data Type: FLOAT
Object Mapping: 0x384-4-9
Group: Control
Units : Amperes
Minimum Value: 00.000A
Maximum Value: 99.999A
Default Value: 00.000A
This parameter allows the user to view the average value for the
Hold coil current on the IntelliVAC Basic Module #4. This coil
current is only valid after the first 200mS after the Close coil is
energized and the Close coil is in the Hold state.
Hold Coil Current for IntelliVAC Base Unit #5
[IB 5 Hold Current]
Parameter Number: 45,_,_,_,_.
Access rule: Get
Data Type: FLOAT
Object Mapping: 0x384-5-9
Group: Control
Units : Amperes
Minimum Value: 00.000A
Maximum Value: 99.999A
Default Value: 00.000A
This parameter allows the user to view the average value for the
Hold coil current on the IntelliVAC Basic Module #5. This coil
current is only valid after the first 200mS after the Close coil is
energized and the Close coil is in the Hold state.