B-4 Parameters
1503-UM054C-EN-P – June 2013
Auxiliary Input Status from IntelliVAC Base Unit #2
[IB 2 Module Aux. Status]
Parameter Number: 2,2,2,2,_.
Access rule: Get
Data Type: BOOL
Object Mapping: 0x384-2-1
Group: Control
Units : -
Minimum Value: 0 = Closed
Maximum Value: 1 = Open
Default Value: 0
This parameter allows the user to view the status of the contactor
Auxiliary input from the IntelliVAC Basic Module #2. A Closed
status refers to the contactor Auxiliary input having no input voltage
which indicates that the contactor is Closed. An Open status refers
to the contactor Auxiliary input having a valid input voltage which
indicates that the contactor is Open. See the Electrical Spec ific ations
section in Table 1.A for the voltage level for a valid Closed and
Open input.
Auxiliary Input Status from IntelliVAC Base Unit #3
[IB 3 Module Aux. Status]
Parameter Number: 3,3,3,_,_.
Access rule: Get
Data Type: BOOL
Object Mapping: 0x384-3-1
Group: Control
Units : -
Minimum Value: 0 = Closed
Maximum Value: 1 = Open
Default Value: 0
This parameter allows the user to view the status of the contactor
Auxiliary input from the IntelliVAC Basic Module #3. A Closed
status refers to the contactor Auxiliary input having no input voltage
which indicates that the contactor is Closed. An Open status refers to
the contactor Auxiliary input having a valid input voltage which
indicates that the contactor is Open. See the Electrical Specifications
section in Table 1.A for the voltage level for a valid Closed and
Open input.