Parameters B-177
1503-UM054C-EN-P June 2013
Status Word for IB5 [IB 5 Status Word]
Parameter Number: 339,_,_,_,_.
Access rule: Get
Data Type: WORD
Object Mapping: 0x384-5-62
Group: Diagnostics
Units : -
Minimum Value: 0
Maximum Value: 0xFFFF
Default Value: 0
This parameter allows the user to view the IB5 Status Word. If a bit
is 0’ then the fault or warning is not present. If a bit is a ‘1’ then the
fault or warning is present.
Table B.43 Status Word for IB5
Bit Enum Text Description
0
Bit 0: unused
unused
1
Bit 1: unused
unused
2
Bit 2: unused
unused
3 Bit 3: Power Up with Contactors Closed Power Up with Contactor Closed IB5
4
Bit 4: Open Coil Open Trip Coil Open on IB5
5
Bit 5: Close Coil Open Close Coil Open on IB5
6
Bit 6: Power Up with Invalid DIPs
Power Up w ith Invalid DIPs on IB5
7
Bit 7: MC Malfunction
MC Malfunction on IB5
8
Bit 8: Drop Out During Hold
Drop Out During Hold on IB5
9
Bit 9: Contactor Fails to Drop Out
Contactor Fails to Drop Out on IB5
10 Bit 10: Power Up with Close Command Power Up w ith Close Command on IB5
11
Bit 11: Long Close Time Long Close Time on IB5
12
Bit 12: Underv oltage w ith Close Command Present Undervoltage with Close Command Present on IB5
13
Bit 13: Long Drop Out Time
Long Drop Out Time on IB5
14
Bit 14: Mechanical Latch Trip Fail
Mechanical Latch Trip Fail on IB5
15
Bit 15: Invalid Command
Invalid Command on IB5