B-40 Parameters
1503-UM054C-EN-P – June 2013
Discrete Output Point Fault Action [DOP Fault Action]
Parameter Number: 72,60,48,36,23.
Access rule: Get/Set
Data Type: BOOL
Object Mapping: 0x1E-1-7
Group: Control
Units : -
Minimum Value: 0 = Go to Fault Value
Maximum Value: 1 = Hold Last State
Default Value: 0
Describes the action on the occurrence of a DOP fault.
Discrete Output Point Fault Value [DOP Fault Value]
Parameter Number: 73,61,49,37,24.
Access rule: Get/Set
Data Type: BOOL
Object Mapping: 0x1E-1-8
Group: Control
Units : -
Minimum Value: 0 = Off
Maximum Value: 1 = On
Default Value: 0
Dictates if any extra action will be performed on the occurrence of a
DOP fault.
Discrete Output Point Idle Action [DOP Idle Action]
Parameter Number: 74,62,50,38,25.
Access rule: Get/Set
Data Type: BOOL
Object Mapping: 0x1E-1-9
Group: Control
Units : -
Minimum Value: 0 = Go to Idle Value
Maximum Value: 1 = Hold Last State
Default Value: 0
Describes the action on the existence of a DOP idle condition.