Product Description 1-9
1503-UM054C-EN-P – June 2013
Table 1.B – Electrical Ratings
Main Input Voltage
(L1 to L2/N)
AC – 110 to 240 V rms, +10/-15%, 47 to 63 Hz
DC – 110 to 250 V, +10/-15%
Main Input Current
(L1 to L2/N)
Description
Contactor
(Amps)
Control Voltage
(AC or DC)
AC Rating DC Rating
Inrush Current 400/800 120/240
25 A peak
(1/2 cycle)
25 A peak
Idle Current
(Maximum w ithout contactor
coil energized)
400/800 120/240 125 mA 35 mA
Hold Current
(maximum)
400/800 120/240 300 mA 100 mA
Close Current
(0.2 sec)
400
120 4.6 A 3.6 A
240 3.4 A 3.3 A
800
240 8.9 A 4.5 A
Trip Current (latch)
(0.2 sec)
400
120 7.0 A 3.7 A
240 3.6 A 2.0 A
800
120 7.0 A 3.3 A
240 4.3 A 1.9 A
Command Inputs
AC – 70 to 240 V rms
DC – 70 to 250 V
Maximum on state current for open or close command:
11mA
AC
@ 276 V AC, 60Hz, T
A
= 60°C
2.4mA
DC
@ 276 V DC, T
A
= 60°C
Minimum on state current for open or close command:
2.5mA
AC
@ 70 V AC, 60Hz, T
A
= 60°C
1.2 mA @ 68 V DC, T
A
= 60°C
Maximum off state current for open or close command:
1.9 µA @ 60 V AC, 60 Hz, T
A
= 60°C
900 µA @ 60 V DC, T
A
= 60°C
Output Contacts
AC – 250 V rms, 5 A, R load; 2 A (reactive), PF = 0.4
DC – 30 V, 5 A, R load; 2 A (reactive), L/R = 7 ms
Standards and
Approvals
CE, cULus, CSA, IEC pending
T
A =
Ambient Temperature
Includes idle current.
Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs.
Consider means of isolating/loading these signals, as required (using interposing relays or load resistors.)
Consult factory for assistance, if needed. The Series C, D and E IntelliVACs are compatible with most PLC outputs,
and have been verified with Rockwell Automation OA type 120V triac outputs. See Chapter 3, Wiring Guidelines.
Includes operation of Auxiliary input and 8 discrete inputs.
Includes module/Contactor Status contacts as well as 2 discrete output contacts.