Parameters B-93
1503-UM054C-EN-P June 2013
Contactor Fails to Pick-Up on IB5
[IB 5 Contactor Fails to Pick-Up]
Parameter Number: 172,_,_,_,_.
Access rule: Get
Data Type: BOOL
Object Mapping: 0x384-5-25
Group: Diagnostics
Units : -
Minimum Value: 0 = Not Present
Maximum Value: 1 = Present
Default Value: 0
This parameter allows the user to view the status of the Contactor
Fails to Pic k-Up warning from the IB5 module. If the bit is0’ then
the warning is not present. If the bit is1’ then the warning is
present. See Contactor Fails to Pick Up in Chapter 4 for a detailed
description of this warning.
Contactor Drop-Out during Hold on IB1
[IB 1 Contactor Drop-out During Hold]
Parameter Number: 173,145,117,89,60.
Access rule: Get
Data Type: BOOL
Object Mapping: 0x384-1-26
Group: Diagnostics
Units : -
Minimum Value: 0 = Not Present
Maximum Value: 1 = Present
Default Value: 0
This parameter allows the user to view the status of the Contactor
Drop-Out during Hold warning from the IB1 module. If the bit is 0’
then the warning is not present. If the bit is1’ then the warning is
present. See Contactor Drop-Out during Hold in Chapter 4 for a
detailed description of this warning.