B-76 Parameters
1503-UM054C-EN-P June 2013
Delay Restart Time for IB1
[IB 1 Delay Restart Time]
Parameter Number: 138,117,96,75,53.
Access rule: Get/Set
Data Type: UINT
Object Mapping: 0x384-1-19
Group: Configuration
Units : Seconds
Minimum Value: 6
Maximum Value: 3600
Default Value: 12
This parameter allows the user to view and set the Delay Restart
Time between successive Open/Trip and Close commands for
contactor IB1. This sets a maximum repetition time for the cycling
of the contactor. It can also be used to prevent rapid restating of the
motor. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.
Delay Restart Time for IB2
[IB 2 Delay Restart Time]
Parameter Number: 139,118,97,76,_.
Access rule: Get/Set
Data Type: UINT
Object Mapping: 0x384-2-19
Group: Configuration
Units : Seconds
Minimum Value: 6
Maximum Value: 3600
Default Value: 12
This parameter allows the user to view and set the Delay Restart
Time between successive Open/Trip and Close commands for
contactor IB2. This sets a maximum repetition time for the cycling
of the contactor. It can also be used to prevent rapid restating of the
motor. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.