INTRODUCTION TO THE DRIVE
FlexPak 3000 49’1340 e
2-4
2.2.7 Regulation (with 95% load change):
Table 2-2 - Tachometer Speed Regulation
Regulation Arrangement
Speed Change with
95% Load Change
Speed Change from
All other Variables
Part Number
Armature Voltage Regulation
with IR Comp.
2-3 % 15% Not applicable.
Closed Loop
with Analog tach 1% 2% -
with Pulse tach 1) 0.01% 0.01% 762.70.00
1) Optional Pulse Tachometer Feedback kit required (See instruction manual 49’1343).
2.2.8 Speed Range:
Operator's Speed Adjustment............................................................................... 0 to rated speed
Specification Speed Range ........................................100:1 based on top speed and tachometer
2.2.9 Drive Efficiency:
Drive Only........................................................................................98.6% (rated load and speed)
Drive and Motor............................................................................................................85% typical
2.2.10 Displacement Power Factor, Power Loss P
V
and Output Current:
Power Factor: 88% typical (rated load & speed, decreasing linearly with speed)
Typical percent speed depends on motor operating speed and motor frame size.
Power Consumption at no load: see P
A
in Table 2-3.
Table 2-3 - Drive Specifications
Unit-Type I
ad
I
anom
I
amax
I
F
(-73/43) I
F
(-03) P
A
P
v
(at I
a nom
)
25 A 25 A 20 A 30 A 4 A 6 A 60 VA 120 W
60 A 60 A 50 A 75 A 4 A 6 A 60 VA 210 W
150 A 150 A 125 A 187 A 10 A 6 A 85 VA 460 W
250 A 250 A 208 A 312 A 10 A 12 A 90 VA 715 W
450 A 450 A 375 A 562 A 10 A 12 A 90 VA 1215 W
800 A 800 A 667 A 1000 A 12 A 12 A 120 VA 2120 W
1200 A, 500V 1200 A 1000 A 1500 A 15 A * - 400 VA 2680 W
1600 A, 500V 1600 A 1334 A 2000 A 15 A * - 400 VA 3750 W
2000 A, 500V 2000 A 1667 A 2500 A 15 A * 400 VA 4600 W
1600 A, 575V 1600 A 1334 A 2000 A 15 A * - 400 VA 3900 W
1600 A, 690V 1600 A 1334 A 2000 A 15 A * - 400 VA 4100 W
I
ad
= Maximum continuous current without overload capability
(
I
ad
= 1.2 x I
a nom
)
I
a nom
= Nominal continuous current with overload capability 50% during 1 minute
every 10 minutes
I
a max
= Maximum current during 1 minute after 9 minutes operation with Ia nom
(I
a max
= 1.5 x
I
a nom
)
I
F
= Field current without overload capability
* A maximum field current of 20 A is permitted, if the power unit blower is switched on
together with the motor field.