APPENDIX G
49’1340 e FlexPak 3000 G-5
Table G.1 - User Quick Reference Table for Input Parameters (continued)
Par.
Parameter Parameter Selection / Pg Initial Factory User Data
No.
Adjustment Range B- Setting Date Setting
Digital Outputs Set-up (on I/O card)
409 DIG OUT 1 SELECT
LEVEL DETECT 1 OUTPUT
LEVEL DETECT 2 OUTPUT
IN CURRENT LIMIT
DRIVE READY
NETW COMM STATUS
NETW IN REG 1
NETW IN REG 2
NETW IN REG 3
13 LEVEL
DETECT 1
OUTPUT
410 DIG OUT 1 CONTACT TYP
NORMAL OPEN
NORMAL CLOSED
13 NORMAL
OPEN
411 DIG OUT 2 SELECT
LEVEL DETECT 1 OUTPUT
LEVEL DETECT 2 OUTPUT
IN CURRENT LIMIT
DRIVE READY
NETW COMM STATUS
NETW IN REG 1
NETW IN REG 2
NETW IN REG 3
14 LEVEL
DETECT 2
OUTPUT
412 DIG OUT 2 CONTACT TYP
NORMAL OPEN
NORMAL CLOSED
13 NORMAL
OPEN
Analog Inputs / Outputs (on I/O card)
413 ANLG IN 1 SIG TYPE
0-10V, ±10V
4-20 mA, 10-50 mA
3 ±10 V
414 ANLG IN 1 ZERO ADJ -200 - 200 3 0
415 ANLG IN 1 GAIN ADJ 0.750 - 2.250 3 1.000
416 ANLG IN 2 ZERO ADJ -200 - 200 4 0
417 ANLG IN 2 GAIN ADJ 0.750 - 2.250 4 1.000
418 ANLG OUT 1 SELECT
CML FEEDBACK
CML REFERENCE
CML ERROR
SPD LOOP FEEDBACK
SPD LOOP REFERENCE
SPD LOOP ERROR
SPD LOOP OUTPUT
SPEED RAMP OUTPUT
SPEED RAMP INPUT TP
SPD SOURCE SELECT OUT
TRIM OUTPUT
ARMATURE VOLTAGE
ANALOG TACH FEEDBACK
PULSE TACH FEEDBACK
ZERO
FULL SCALE
POWER OUTPUT
OCL REFERENCE
OCL RAMP OUTPUT
OCL FEEDBACK
OCL OUTPUT
FIELD REFERENCE
FIELD FEEDBACK
NETW IN REG 1
NETW IN REG 2
NETW IN REG 3
5 ZERO
Vista de pagina 204