APPENDIX G
49’1340 e FlexPak 3000 G-1
User Quick Reference Table
Table G.1 - User Quick Reference Table for Input Parameters
Par.
Parameter Parameter Selection /
Pg.
Initial Factory User Data
No.
Adjustment Range B- Setting Date Setting
000 CONTROL SOURCE SELECT
KEYPAD
SERIAL
TERMBLK
NETWORK
11 KEYPAD
001 ACCELERATION TIME 0.1 - 300.0 sec 1 5.0 sec
002 DECELERATION TIME 0.1 - 300.0 sec 12 5.0 sec
003 MINIMUM SPEED 0 - MAXIMUM SPEED (P.004) 29 0 (*RPM)
004 MAXIMUM SPEED 1 - TOP SPEED (P.011) 26 500 (*RPM)
005 POSITIVE CURRENT LIM 0 - MAXIMUM CURRENT
(P.007) in % FLA (P.008)
43 150% P.008
006 NEGATIVE CURRENT LIM 0 - MAXIMUM CURRENT
(P.007) in % FLA (P.008)
32 150% P.008
007 MAXIMUM CURRENT 25 - 200 %FLA (P.008) 25 150% P.008
008 MOTOR RATED ARM AMPS 0 - 3000.0 A 31 unit type dep.
009 MOTOR RATED ARM VOLTS 160 - 675 VDC or
240 - 1000 VDC (type 690 VAC)
31 400 V
010 CT TURNS RATIO
25 A Unit: 208
60 A Unit: 416
150 A Unit: 833
250 A Unit: 2000
450 A Unit: 3000
800 A Unit: 5230
1200 A Unit: 8000
1600-2000 A Unit: 10500
11 depending on
unit type
32767 Tp/Tn
011 TOP SPEED 5 - 5000 RPM 51 500 RPM
012 JOG SPEED 1 0 - MAXIMUM SPEED (P.004)
in *rpm
23 250 (*RPM)
013 JOG ACCEL/DECEL TIME 0.1 - 300.0 sec 23 3.0 sec
014 S-CURVE ROUNDING 0 - 50% (0% = no rounding) 45 0%
015 REVERSE DISABLE
OFF
ON
44 S-6R = OFF
S-6 = ON
017 JOG SPEED 2 0 - MAXIMUM SPEED (P.004)
in *rpm
23 250 (*RPM)
018 RAMP STOP DECEL TIME 0.1 - 300.0 sec 44 5.0 sec
019 SPD LOOP SCAN TIME 0 = 5 msec 1 = 10 msec 49 5 msec
Analog Inputs
100
(2)
ANLG AUTO SIGNAL TYPE
0 -10 V
• ±10 V
4-20 mA
10-50 mA
2 0-10 V
101 ANLG AUTO GAIN ADJ 0.750 - 1.250 2 1.000
102 ANLG AUTO ZERO ADJ -200 - +200 2 0
103 AUTO REFERENCE SELECT
ANALOG
FREQUENCY IN
8 ANALOG
104 ANLG MAN REF GAIN ADJ 0.750 - 1.250 4 1.000
(*) Or user defined unit.
(2) Jumpers J10 and J12 must be set for the type of auto reference selected.