INSTALLATION AND WIRING
49’1340 e FlexPak 3000 3-13
Table 3.6 - User Device Connections to the Regulator Board Terminal Strip
User Device Regulator Board Terminal Strip Numbers
RUN 1 (+24V) and 2
STOP 1 (+24V) and 3
JOG 1 (+24V) and 4
REV/FWD 1 (+24V) and 5
AUTO/MAN reference select 1 (+24V) and 6
INTERLOCK 9 and 11 (+24V)
FAULT/ALARM RESET 10 and 11 (+24V)
DIGITAL INPUT 0 12 and 14 (+24V)
MOTOR THERMOSTAT 13 and 14 (+24V)
24V SUPPLY COMMON 15 (+24V COM)
SPEED REFERENCE POTENTIOMETER:
High Side (+10 ISOL)
16
Wiper (+ MAN REF) 17
Low Side (COM) 18
AUTO REFERENCE: (+) 19
(-) 20
TACHOMETER (Analog):
High Range (Jumper J14 in position HIGH)
21
Low Range (Jumper J14 in position LOW) 22
Common 23
ANALOG OUT1 (Metering) 24 and 25 (common)
ANALOG OUT2 (Metering) 25 (common) and 26
RUNNING (Indicator) 27 and 28
ALARM (Indicator) 29 and 30
NO FAULT (Indicator) 31 and 32
X1
K10 K10T K1 K1M
5
6
34
MCR
K10
K1
K1M
K10T
Figure 3-8b – Main Contactor Sequencing Connection Diagram - Example