APPENDIX G
FlexPak 3000 49’1340 e
G-2
Table G.1 - User Quick Reference Table for Input Parameters (continued)
Par.
Parameter Parameter Selection / Pg Initial Factory User Data
No.
Adjustment Range B- Setting Date Setting
105 ANLG MAN REF ZERO ADJ -200 - +200 4 0
106 MANUAL REF SELECT
• ANALOG
• MOP
25 ANALOG
107 TRIM REF REGISTER + 100.0% 52 0%
108 TRIM REFERENCE SELECT
• ANALOG MANUAL
• ANALOG IN 1
• NETW IN REG 1
• NETW IN REG 2
• NETW IN REG 3
• ANALOG IN 2
• REGISTER
51 REGISTER
109 TRIM RANGE 0 - +100.0% 51 0.0%
110 TRIM MODE SELECT
• NO TRIM
• INCREMENTAL
• PROPORTIONAL (DRAW)
51 NO TRIM
111 AUTO MODE MIN BYPASS
• OFF
• ON
8 OFF
112 AUTO MODE RAMP BYPASS
• OFF
• ON
8 OFF
113 STOP SPEED THRESHOLD 0 - MAXIMUM SPEED (P.004)
in *RPM
50 0 (*RPM)
114
(3)
STOP MODE SELECT
• RAMP
• COAST/DB
• CURRENT LIMIT
49 RAMP
115 MOP ACCEL TIME ACCELERATION TIME (P.001) -
300.0 seconds
29 5.0 seconds
116 MOP RESET ENABLE
• OFF
• ON
30 OFF
117 PRESET SPEED 1 MINIMUM SPEED- MAX SPEED 43 250 *RPM
118 PRESET SPEED 2 MINIMUM SPEED- MAX SPEED 43 250 *RPM
119 PRESET SPEED 3 MINIMUM SPEED- MAX SPEED 43 250 *RPM
120 MOP DECEL TIME DECEL.. TIME (P.002)- 300 sec 30 5.0 seconds
121 JOG OFF DELAY TIME 0.0 to 10.0 seconds 23 1.0 seconds
122 STOP DECEL SELECT
• 1 = DECELERATION TIME
• 2 = RAMP STOP DECEL TIME
48 1
Feedback Selection
200 FEEDBACK SELECT
• ARMATURE VOLT
• DC TACH
• PULSE TACH
• AC TACH
14 ARM VOLT for
S-6
DC TACH for
S-6R
201 ANALOG TACH GAIN ADJ 0.750 - 1.250 1 1.000
202 ANALOG TACH ZERO ADJ -200 - +200 2 0
203 ANLG TACH VOLTS/1000 18.0 - 200.0 V/1000 RPM 6
60V/1000 RPM
204 ARM VOLTAGE GAIN ADJ 0.750 - 1.250 7 1.000
205 ARM VOLTAGE ZERO ADJ -200 - +200 V 8 0 V
206 IR COMPENSATION 0 - 50 %FLA 22 0% FLA
(*) Or user defined unit.
(3) If drive is configured as a current regulator,
only COAST/DB can be selected.
Comentarios a estos manuales