APPENDIX G
FlexPak 3000 49’1340 e
G-6
Table G.1 - User Quick Reference Table for Input Parameters (continued)
Par.
Parameter Parameter Selection / Pg Initial Factory User Data
No.
Adjustment Range B- Setting Date Setting
419 ANLG OUT 1 SIG TYPE
0-10 V, ±10 V, 4-20 mA
6 ±10 V
420 ANLG OUT 1 GAIN ADJ 0.500 - 1.300 5 1.000
421 ANLG OUT 2 SELECT
same as above for P.418
7 ZERO
422 ANLG OUT 2 GAIN ADJ 0.500 - 1.300 6 1.000
Frequency Inputs/Outputs (on I/O card)
423 FREQ IN ZERO 2.0 - FREQ IN FULL SCALE kHz 19 2.0 kHz
424
FREQ IN FULL SCALE
2.0 - 250.0 kHz 19 250.0 kHz
425 FREQ OUT SELECT
same as above for P.418
20 ZERO
426 FREQ OUT ZERO
2.0 - FREQ OUT FULL SCALE kHz
21 2.0 kHz
427 FREQ OUT FULL SCALE 2.0 - 250.0 kHz 20 250.0 kHz
428 DIG IN 0 SELECT
1 = BRUSH WEAR
2 = JOG SPEED SELECT
3 = OCL ENABLE
12 1
Field Regulator Set-up
500 ENHANCED FLD VOLT ADJ
0 - 180 (J21 = B-C)
14 84
501 FIELD ECONOMY DELAY 0 - 27 minutes 16 5 minutes
510 MOTOR HOT FLD AMPS 0.11 - installed supply rating
(4.00, 10.00, or 15.00 A)
30 0.1 A
511 FIELD ECONOMY REF 0 - 100% 16 0%
512 FIELD LOSS THRESHOLD
Armature voltage regulators:
50 - 100% of
MOTOR HOT FLD AMPS (P.510)
Speed regulators: 0 - 100% of
MOTOR HOT FLD AMPS (P.510)
17 60% of
MOTOR HOT
FLD AMPS
513 FIELD REF REGISTER 0 to MOTOR HOT FLD AMPS
(P.510)
18 MOTOR HOT
FLD AMPS
514 FIELD PI PROP GAIN 0.01 - 128.00 17 0.50
515 FIELD PI LEAD FREQ 0.01 - 56.50 rad/s 17 1.50 rad/s
516 FLD FEEDBACK GAIN ADJ 0.900 - 1.100 18 1.000
517 FIELD AUTO WEAKEN
DISABLED
ENABLED
17 DISABLED
518 FLD WEAKEN THRESHOLD 0 to 120% of
MOTOR RATED ARM VOLTS
(P.009)
19 95% of
MOTOR
RATED ARM
VOLTS
519 FLD WEAKEN PROP GAIN 0.01 - 128.00 19 1.60
520 FLD WEAKEN LEAD FREQ 0.01 - 56.50 rad/s 18 0.50 rad/s
521 FIELD REF SELECT
1 = REGISTER
2 = ANALOG MAN TRIM REF
3 = ANALOG IN 1
4 = ANALOG IN 2.
18 1
587 FIELD DELTA HIGH LIM 0 - 180 degree 16 130 degree
Thyristor Firing check
600 OPEN SCR SENSITIVITY 0 - 100% 41 50%
601 OPEN SCR TRIP THRESH 800 - 4000 41 1600