102 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
ArmorStart LT EtherNet/IP
Parameters
Introduction
This chapter describes each programmable parameter and its function.
Parameter Programming
Each Distributed Motor Controller type will have a common set of parameters
and a set of parameters that pertain to the individual starter type. Parameters
41
68 are common to all ArmorStart LTs.
Bulletin 290E/291E
Basic Status Group
IMPORTANT
Parameter setting changes take effect immediately unless otherwise noted
in the parameter listing. These changes maybe immediate even during the
"running" status.
PhaseL1Current
This parameter determines the actual
Phase L1 current.
Parameter Number 1
Access Rule GET
Data Type INT
Group Basic Status
Units x.xx Amps
Minimum Value 0
Maximum Value 32767
Default Value 0
PhaseL2Current
This parameter determines the actual
Phase L2 current.
Parameter Number 2
Access Rule GET
Data Type INT
Group Basic Status
Units x.xx Amps
Minimum Value 0
Maximum Value 32767
Default Value 0