Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 127
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
Bit
Function:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
——————————————— X Pt00
—————————————— X — Pt01
————————————— X —— Pt02
———————————— X ——— Pt03
——————————— X ———— Pt04
—————————— X ————— Pt05
XXXXXXXXXX—————— Reserved
NetworkStatus
The parameter provides the status
of the network connections.
Parameter Number 9
Access Rule GET
Data Type WORD
Group Basic Status
Units —
Minimum Value 0
Maximum Value 0xDF
Default Value 0
Bit
Function:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
——————————————— X ExplicitCnxn
—————————————— X — IOConnection
————————————— X —— ExplicitCnxnFlt
———————————— X ——— IOCnxnFault
——————————— X ———— IOCnxnIdle
—————————— X ————— Reserve
————————— X —————— DLREnabled
——————— X ——————— DLRFlt
XXXXXXXX———————— Reserved
DLXControlStatus
The parameter provides the DeviceLogix
Control Status.
0 = Controlled in Logix Programs
1 = Controlled in local DLX programs.
Parameter Number 10
Access Rule GET
Data Type UINT
Group Basic Status
Units —
Minimum Value 0
Maximum Value 0x1FFF
Default Value 0