Chapter 5 Diagnostics
Fault Diagnostics
Fault diagnostics capabilities built in the ArmorStart LT Distributed Motor
Controller are designed to help you pinpoint a problem for easy troubleshooting
and quick restarting.
Protection Faults
Protection faults will be generated when potentially dangerous or damaging
conditions are detected. Protection faults are also known as “trips” or “faults.
These faults will be reported in multiple formats, including:
Bit enumeration in the TripStatus parameter (parameter 16) used as
discrete bits or in DeviceLogix
In the ArmorStart LT web server for ArmorStart EtherNet/IP version
As a sequence of LED flashes on the ECM
MS – Module Status
LED
The bicolor (green/red) LED indicates the
status of the module.
Flashing bicolor (red/green) indicates a
self-test on power up.
Flashing green indicates the device has not
been assigned an IP address.
Steady green indicates the device is
configured and operational.
Flashing red indicates a resettable
protection fault exists or the node address
switches have been changed without a
power cycle and do not match the in-use
configuration.
Steady red indicates a non-resettable
protection fault exists.
I/O Status
Enunciators 0…5
LEDs
Six yellow LEDs are numbered 0…5 and
indicate the status of the input/output
connectors. One LED for each I/O point.
Yellow is illuminated when input is valid or
output is on.
Off when input is not valid or the output is
not turned on.
Reset Button The blue reset button will cause a
protection fault reset to occur.
——
Table 25 - ArmorStart LT Status and Diagnostics Indicators
Indicator Description Color_1 Color_2
LED Flash Bit Enumeration Bulletin 290E/291E Trip Status Bits Bulletin 294E Trip Status Bits
10OverloadTrip OverloadTrip
2 1 PhaseLossTrip PhaseLShortTrip
32UnderPowerTrip UnderPowerTrip
4 3 SensorShortTrip SensorShortTrip
5 4 PhaseImbalTrip OverCurrentTrip
65NonVolMemoryTrip NonVolMemoryTrip
76reserved ParamSyncTrip
87JamTrip DCBusOrOpenDiscnnct
98StallTrip StallTrip
10 9 UnderloadTrip OverTemperature
11 10 reserved GroundFault
12 11 reserved RestartRetries
13 12 reserved DriveHdwFault