Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
Bit
Function
1514131211109876543210
——————————————— X OverloadWarning
—————————————— X Reserved
————————————— X ——
UnderPowerWarn
———————————— X ——— Reserved
——————————— X ———— PhasImbalanceWarn
————————— X X ————— Reserved
———————— X ——————— JamWarning
——————— X ———————— Reserved
—————— X ————————— UnderloadWarning
XXXX——————— Reserved
X —————————————— UnswitchedPwrWarn
X ——————————————— ConfigWarning
ProtectFltReset
This parameter resets a Protection Fault by
setting the bit to 1.
0 = NoAction
0 > 1 = ResetFault
Parameter Number 44
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
RunNetFltAction
This parameter in conjunction with
Parameter 46 (RunNetFltValue) defines
how the starter will respond when
a fault occurs.
0 = GoToFaultValue
1 = HoldLastState
Parameter Number 45
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0