236 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Appendix C Using DeviceLogix™
ArmorStart LT Bulletin 294E Example Configuration
Hardware & Software Versions Used in this example
RSLogix 5000 Revision 19
Download AOP from the Support website:
http://support.rockwellautomation.com/controlflash/LogixProfiler.asp
Hardware:
294E-FD2P5Z-G1 — ArmorStart LT
1606-XLP72E — Power Supply
1783-EMS08TA — Stratix Ethernet switch
1756-L63 system set — Control Logix
1756-EN2TR — EtherNet/IP module for Control Logix
The IP address of the Hardware will be preset to as followed:
The Armorstart LT control power wiring example used
Figure 1: Control Power Wiring Example
Item Description IP Address
1 ArmorStart LT 192.168.1.36
2 1756-EN2TR 192.168.1.32
3 PC 192.168.1.89
Outputs
Inputs
EtherNet
Comms
A3
A1
A2
O
Switched Control Power
Unswitched Control Power
Motor
Control
Motor
Controller
Class 2
External
24VDC Power
Supply
Disconnect
24VDC
+
-
L1 L2
L3
T1 T2
T3
* Control power output is determined by disconnect status
*
ArmorStart LT
L
N
Single External Power Supply