Rockwell-automation 294E ArmorStart LT EtherNet/IP Version - User Manu Manual de usuario Pagina 36

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 252
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 35
36 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 1 Product Overview
Bulletin 290E
With the KeypadMode parameter (parameter 66) set to 1 = Maintained, pressing
the buttons reacts like a maintained switch.
With the KeypadMode parameter (parameter 66) set to 0 = Momentary,
pressing the buttons reacts like a momentary switch.
Bulletin 291E
With the KeypadMode parameter (parameter 66) set to 1 = Maintained, pressing
the buttons reacts like a maintained switch.
With the KeypadMode parameter (parameter 66) set to 0 = Momentary,
pressing the buttons reacts like a momentary switch.
Key Press
Current Mode
OFF HAND AUTO
AUTO Auto Mode — Motor Off
HAND If no fault, Motor On
OFF Motor turns Off Motor turns Off
FAULT PRESENT Motor turns Off Motor turns Off
Key Press
Current Mode
OFF Key HAND AUTO Key
NO KEY PRESSED Motor Off
AUTO Auto Mode — Motor Off
HAND If no fault, Motor On
OFF Motor Off Motor Off
PROTECTION FAULT PRESENT Motor Off
Key Press
Current Mode
OFF HAND AUTO
FWD/REV FWD LED Set REV LED
REV LED Set FWD LED
——
AUTO Auto Mode — Motor Off
HAND If no fault, Motor On
OFF Ignore Motor Off Motor Off
PROTECTION FAULT PRESENT Ignore Motor Off
Key Press
Current Mode
OFF HAND AUTO
NO KEY PRESSED Motor Off
FWD/REV FWD LED Set REV LED
REV LED Set FWD LED
——
AUTO Auto Mode — Motor Off
HAND If no fault, Motor On
OFF Motor Off Motor Off
PROTECTION FAULT PRESENT Motor Off
Vista de pagina 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 251 252

Comentarios a estos manuales

Sin comentarios