Bulletin 290E/291E/294E Programmable Parameters Chapter 4
ATTENTION:
If a hazard of injury due to movement of equipment or material exists, an
auxiliary mechanical braking device must be used.
This feature should not be used with synchronous or permanent magnet
motors. Motors may be demagnetized during braking.
ReverseDisable
Enables/disables the function that allows
the direction of the motor rotation to be
changed.
0 = Enabled
1 = Disabled
Parameter Number 77
Related Parameters
Access Rule GET/SET
Data Type UINT
Group Advanced Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
FlyingStartEn
Sets the condition that allows the drive
to reconnect to a spinning motor
at actual RPM.
0 = Disabled
1 = Enabled
Parameter Number 78
Access Rule GET/SET
Data Type UINT
Group Advanced Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Time
[DC Brake Level]
[DC Brake Time]
Stop Command
Speed
Voltage
Volts Speed
[DC Brake Level]
[DC Brake Time]
Time
Voltage
Speed
Stop Command
Volts Speed
DC Injection Braking Mode
Ramp-to-Stop Mode
}
}
}
}
Stop drive before changing this
parameter.
O