Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 123
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
ULTripDelay
This parameter determines the time below
Underload Level before the unit will trip.
Parameter Number 77
Access Rule GET
Data Type USINT
Group Advanced Config.
Units x.x secs
Minimum Value 1
Maximum Value 25.0
Default Value 5.0
ULTripLevel
This parameter determines the
Underload Trip Level as a percentage
of Full Load Amps.
Parameter Number 78
Access Rule GET
Data Type USINT
Group Advanced Config.
Units %FLA
Minimum Value 10
Maximum Value 100
Default Value 50
ULWarningLevel
This parameter determines the
Underload Warning Level as a
percentage of Full Load Amps.
Parameter Number 79
Access Rule GET
Data Type USINT
Group Advanced Config.
Units %FLA
Minimum Value 10
Maximum Value 100
Default Value 70