130 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
Bit
Function
1514131211109876543210
——————————————— X OverloadTrip
—————————————— X PhaseShortTrip
———————————— X —— UnderPowerTrip
———————————— X ——— SensorShortTrip
——————————— X ———— OverCurrentTrip
—————————— X ————— NonVolMemoryTrip
————————— X —————— ParamSyncTrip
———————— X ———————
DCBusTrip/
OpenDisconnect
——————— X ———————— StallTrip
—————— X ————————
OverTemperature
————— X —————————— GroundFault
———— X ——————————— RestartRetries
——— X ———————————— DriveHdwFault
—— X ————————————— OutputShortTrip
X —————————————— UserDefinedTrip
X ——————————————— HardwareFltTrip
WarningStatus
This parameter provides the current
warning condition.
Parameter Number 17
Access Rule GET
Data Type WORD
Group Trip Status
Units
Minimum Value 0
Maximum Value 0xC044
Default Value 0
Bit
Function
1514131211109876543210
—————————————— X X Reserved
————————————— X ——
UnderPowerWarn
—————————— X X X ——— Reserved
————————— X —————— DriveParamInit
XXXXXXX——————— Reserved
X —————————————— UnswitchedPwrWarn
X ——————————————— ConfigWarning
Vista de pagina 129