34 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 1 Product Overview
Fault Diagnostics
Fault diagnostics capabilities built in the ArmorStart LT Distributed Motor
Controller are designed to help you pinpoint a problem for easy troubleshooting
and quick re-starting.
Protection Faults
Protection faults will be generated when potentially dangerous or damaging
conditions are detected. Protection faults are also known as “trips” or “faults.
These faults will be reported in multiple formats, including:
Bit enumeration in the TripStatus parameter 16 in DeviceLogix
In the ArmorStart LT web server for ArmorStart EtherNet/IP version
As a sequence of LED flashes on the ECM
Table 6 - Protection Faults
Cannot be disabled.
LED Flash Bit Enumeration Bulletin 290E/291E Trip Status Bits Bulletin 294E Trip Status Bits
10OverloadTrip OverloadTrip
2 1 PhaseLossTrip PhaseLShortTrip
32UnderPowerTrip UnderPowerTrip
4 3 SensorShortTrip SensorShortTrip
5 4 PhaseImbalTrip OverCurrentTrip
65NonVolMemoryTrip NonVolMemoryTrip
76reserved ParamSyncTrip
8 7 JamTrip DCBusOrDiscnnct
98StallTrip StallTrip
10 9 UnderloadTrip OverTemperature
11 10 reserved GroundFault
12 11 reserved RestartRetries
13 12 reserved DriveHdwFault
14 13 OutputShortTrip OutputShortTrip
15 14 UserDefinedTrip UserDefinedTrip
16 15 HardwareFltTrip HardwareFltTrip