Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 119
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
Miscellaneous Configuration Group
Input03Function
This parameter determines the special
function for User Input 3:
0 = NoFunction
1 = FaultReset
2 = MotionDisable
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease
These choices are level sensitive. All
others are edge sensitive
Parameter Number 61
Access Rule GET/SET
Data Type USINT
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 4
Default Value 0
Input04Function
This parameter determines the special
function for User Input 4:
0 = NoFunction
1 = FaultReset
2 = MotionDisable
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease
These choices are level sensitive. All
others are edge sensitive
Parameter Number 62
Access Rule GET/SET
Data Type USINT
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 4
Default Value 0
Input05Function
This parameter determines the special
function for User Input 5:
0 = NoFunction
1 = FaultReset
2 = MotionDisable
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease
These choices are level sensitive. All
others are edge sensitive
Parameter Number 63
Access Rule GET/SET
Data Type USINT
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 4
Default Value 0
NetworkOverride
This parameter allows for the local logic to
override a Network fault.
0 = Disable
1 = Enable
Parameter Number 64
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0