Rockwell-automation 294E ArmorStart LT EtherNet/IP Version - User Manu Manual de usuario Pagina 115

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 252
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 114
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 115
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
User I/O Configuration Group
RunNetFltValue
This parameter determines how the starter
will be commanded in the event of a fault.
State the starter will go to on a NetFlt if
Parameter 45 (RunNetFltAction) = 1
(GotoFault-Value).
0 = OFF
1 = ON
Parameter Number 46
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
RunNetIdlAction
This parameter in conjunction with
Parameter 48 (RunNetIdlValue) defines
how the starter will respond when a
network is idle as determined by
Parameter 48.
0 = GoToIdleValue
1 = HoldLastState
Parameter Number 47
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
RunNetIdlValue
This parameter determines the state that
starter assumes when the network is idle
and Parameter 47 (RunNetIdlAction) is set
to 1.
0 = OFF
1 = ON
Parameter Number 48
Access Rule GET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
IOPointConfigure
This parameter determines the point that
is configured:
0 = Input
1 = Output
Parameter Number 49
Access Rule GET/SET
Data Type WORD
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 0x3F
Default Value 0
Vista de pagina 114
1 2 ... 110 111 112 113 114 115 116 117 118 119 120 ... 251 252

Comentarios a estos manuales

Sin comentarios