Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 139
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
WarningEnable
This parameter enables a warning
by setting the bit to 1.
Parameter Number 43
Access Rule GET/SET
Data Type WORD
Group Starter Protection
Units
Minimum Value 0
Maximum Value 0xC044
Default Value 0
Bit
Function
1514131211109876543210
—————————————— X X Reserved
————————————— X ——
UnderPowerWarn
—————————— X X X ——— Reserved
————————— X —————— DriveParamInit
XXXXXXX——————— Reserved
X —————————————— UnswitchedPwrWarn
X ——————————————— ConfigWarning
ProtectFltReset
This parameter resets a Protection Fault
by setting the bit to 1.
0 = NoAction
0 > 1 = ResetFault
Parameter Number 44
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
RunNetFltAction
This parameter in conjunction with
Parameter 46 (RunNetFltValue) defines
how the starter will respond when a
network fault occurs as determined.
0 = GoToFaultValue
1 = HoldLastState
Parameter Number 45
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0