Rockwell-automation 294E ArmorStart LT EtherNet/IP Version - User Manu Manual de usuario Pagina 167

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 252
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 166
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 167
Specifications Chapter 6
Input and Output Ratings
Input
Supply Voltage Unswitched power A3/A2
Type of Inputs 24V DC current sinking
Connection Type Single keyed M12, quick disconnect
Input per Connection 1/each
Rated Operating Voltage 24V DC
On-State Input Voltage (pin 4) 10…26.4V DC, nominal 24V DC
Off-State Input Voltage 5V DC
On-State Input Current (pin 4) 1…3.7 mA, 2.6 mA @ 24V DC
Off-State Input Current <1.5 mA
Maximum Sensor Leakage Current <2.5 mA
Maximum Number of Input Devices 6
Maximum Sensor Sourcing Current (pin 1) 50 mA per point (max 300 mA total for sourcing one device)
Sensor Operating Voltage Range 19.2…26V DC
Input Bounce Filter
(Software Configurable)
Off-On or On-Off: 0.5 ms + 64 ms
Filtering 100 μs
DeviceLogix I/O Response 2 ms (500 Hz)
Output
Supply Voltage (Switched Power) A1/A2
Type of Outputs DC sourcing
Load Types Resistive or light inductive
Utilization Category (IEC) DC-1, DC-13
Output State Normally Open (N.O.)
Connection Type Single keyed M12, quick disconnect
Output per Connection 1/each
Overcurrent Protection 1.5 A (the sum of all outputs cannot exceed this value)
Rated Insulation Voltage (U
i
) UL: 1500V AC, IEC: 2000V AC
Rated Operating Voltage (U
e
) 19.2…26.4V DC
Maximum Blocking Voltage 35V DC
Nominal Operating Current (I
e
) 500 mA per point
Maximum Thermal Current (I
the
) 500 mA per point
Maximum Off-state Leakage Current 1 μA
Maximum Number of Outputs 6
Surge Suppression Integrated diode to protect against switching loads
Input ON-to-OFF delay time is the time from a valid input signal to recognition by the module.
If an output exceeds 1.5 A for greater than 7 ms, a fault is generated.
Vista de pagina 166
1 2 ... 162 163 164 165 166 167 168 169 170 171 172 ... 251 252

Comentarios a estos manuales

Sin comentarios