Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 175
Specifications Chapter 6
Environmental Ratings
Operating Temperature Range
-20…+40°C (-4…+104°F)
50 °C (122 °F) without derating, when properly rated line reactors are installed
in branch circuit.
Storage and Transportation
Temperature Range
–25...+85 °C (–13…+185 °F)
Altitude 1000 m
Humidity 5…95% (non-condensing)
Pollution Degree 3
Enclosure Ratings IP66/UL Type 4/12 ➊
Approximate Shipping Weight 7.3 kg (16 lb)
➊ IP66/UL Type 4 is available with gland options G1-3. IP66/ UL Type 4/12 available with G1 and G3 gland option.
Mechanical Ratings
Resistance to Shock
Operational 30 G (exceeds IEC 61800-5-1)
Non-Operational 50 G (exceeds IEC 61800-5-1)
Resistance to Vibration
Operational 2.5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)
Non-Operational 5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)
Disconnect Lock Out Maximum of 3/8 in. (9.5 mm) diameter lock shackle or hasp
Disconnect LOTO Locks Up to 2 locks or hasps are supported
Disconnect Mechanical Life 200 000 operations
Power Terminals Motor Terminals Control Terminals PE/Ground Source Brake
Wire Size ➊
(2) #18 …#10 AWG
(0.8…5.2 mm
2
) per
terminal
#18…#10 AWG
(0.8…5.2 mm
2
) per
terminal
(2) #18 …#10 AWG
(0.8…5.2 mm
2
) per
terminal
(2) #16 …#10 AWG
(1.3…5.2 mm
2
) per
terminal
#16 …#10 AWG
(1.0…4.0 mm
2
) per
terminal
Wire Type Multi-strand copper wire
Tightening Torque 10.6 ± 2 lb•in (1.2 ± 0.2 N•m)
18 ± 2 lb•in
(2 ± 0.2 N•m)
4.8 ± 2 lb•in
(0.5 ± 0.2 N•m)
Wire Strip Length 0.35 ± 0.01 in. (9 ± 2 mm)
Power Rating 600V AC/25 Amp 600V AC/10 Amp 600V AC/10 Amp — 600V AC/10 Amp
Emission and Immunity Ratings
Emission
Conducted
EN 55011
Class Group 2
Radiated
Electrostatic Discharge 4 kV contact, 8 kV air
Radio Frequency Electromagnetic Field
EN 61800-3
10V/m, 80 MHz…1 GHz
Immunity
Fast Transient
2 kV (Power)
2 kV (PE)
1 kV (Communication and control)
Surge Transient 1 kV (12)
L-L
, 2 kV (2)
L-N
(earth)
Radio Frequency Conducted Disturbance 10V, 150 kHz…80 MHz
➊ When two wires used in terminal block both wires are to be of same wire AWG