Rockwell Automation Publication IASIMP-QS034A-EN-P - October 2012 247
Logic Module Customization Appendix B
State Display Tag Modifications
Each instance of any MachineSTATE_Add-On Instruction instruction contains an embedded string tag that sets
the Machine.StateDisplay tag following a state change. The Machine.StateDisplay tag is referenced by the HMI
to display the current or active machine state. In this example, you modify the embedded string tag.
1. Right-click the Add-On Instruction tag name and choose Open Instruction Logic.
2. Navigate to rung 5, right-click State_Name, and choose Monitor “State_Name”.