54 Rockwell Automation Publication MPMA-UM001B-EN-P - November 2010
Chapter 6 Configuration Guidelines
3. Reduce the default Stopping Time Limit from 10 seconds to 0.5 seconds.
4. Select the Tune tab in the Axis Properties dialog box and enter the
following parameters:
Travel Limit. Set to a maximum of the travel length of the linear stage.
Speed (velocity).
Torque/Force.
5. On the Tune tab, click Start Tuning to access the Motion Initiation dialog
box.
IMPORTANT
To prevent the carriage from moving, or falling when installed in
a vertical orientation, the Stopping Time Limit must be set to
0.99 seconds or less.
IMPORTANT
Only check Torque Offset, as shown below, if the linear stage is
installed in a non-horizontal mount position.