Pico GFX Control Commands 7-33
High-speed counter: CH01 – CH04
Table 6.124 Index 0 – Bit IO
Bit76543 2 1 0
FB input Data 1 ––––
EN
(3)
(3) Counter enable
FB output Data 3 –––––
ZE
(1)
(1) Zero: Status 1 if the value of the function block output QV (the counter status) equals zero
FB
(2)
(2) Fall below: Status 1 if the actual value F lower setpoint
OF
(4)
(4) Overflow: Status 1 if the actual value f upper setpoint
Table 6.125 Telegram Structure
Byte Meaning Value (hex), sent by
Master Slave Master Slave
Attribute ID
Read 92
Write B2
0 Response:
Read successful C2
Write successful C1
Command rejected C0
0 1 Type 16 16
1 2 Instance 01 – 04 01 – 04
2 3 Index Table 6.126 Table 6.126
3 – 6 4 – 7 Data 1 – 4
Read operation 00 depending on
index,Table 6.127
Write operation depending on
index,Table 6.127
00