Publication 1760-UM003A-EN-P - September 2005
Pico GFX Control Commands 7-3
Table 6.68 Telegram Structure
Byte Meaning Value (hex), sent by
Master Slave Master Slave
Attribute ID
Read 93
Write B3
0Answer
Read successful C2
Write successful C1
Command rejected C0
01Len 05 05
1 2 Index 00 00
2 – 6 3 – 7 Data 1 – 5
Read operation 00 Table 6.69
Write operation Table 6.69 00
Table 6.69 Byte 2 to 6 (master) or Byte 3 to 7 (slave): Data 1 to 5
Byte Content Operand Value
(hex)
Master Slave
2 3 Data 1 Hour 0 to 23 00 – 17
3 4 Data 2 Minute 0 to 59 00 – 3B
4 5 Data 3 Day Day (1 to 28; 29, 30, 31
; depending on month and year)
01 – 1F
5 6 Data 4 Month 1 to 12 01 – 0C
6 7 Data 5 Year 0 to 99 (corresponds to 2000-2099) 00 – 63