Publication 1760-UM003A-EN-P - September 2005
Pico GFX Control Commands 7-49
Year time switch: HY01 – HY32
The data in the following table is shown in the Motorola format
although it is actually transferred in Intel format.
Table 6.158 Telegram Structure
Byte Meaning Value (hex), sent by
Master Slave Master Slave
Attribute ID: Read 92
0 Response:
Read successful C2
Command rejected C0
0 1 Type 1D 1D
1 2 Instance 01 – 20 01 – 20
2 3 Index Table 6.159 Table 6.159
3 – 6 4 – 7 Data 1 – 4 00 depending on
index,Table 6.160
Table 6.159 Operand overview
Index
(hex)
Operand read write
00 Bit IO Table 6.160 x
01 Mode/Parameter
02 Parameters Table 6.161 x
Channel A
03 Channel B
04 Channel C
05 Channel D
Table 6.160 Index 0 – Bit IO
Bit76543 2 1 0
FB output Data 3
Q
(1)
(1) Status 1 if the switch-on condition is fulfilled.