Publication 1760-UM003A-EN-P - September 2005
7-62 Pico GFX Control Commands
02 Setpoint 1:
Time setpoint 1
I1 x
c
(1)
03 Setpoint 2:
Time setpoint 2
(with timing relay with 2
setpoints)
I2 x
c
(1)
04 Actual value:
Time elapsed in Run mode
QV x
(1) The value can only be written if it is assigned to a constant in the program.
TIP
The data for index 2 to 4 is transferred as a 32-bit
value in Intel format (Data 1 – Low Byte to Data 4 –
High Byte).
Table 6.192 Index 0 – Bit IO
Bit76543 2 1 0
FB input Data 1
ST
(1)
(1) Stop, the timing relay is stopped (Stop coil)
EN
(2)
(2) Enable, the timing relay is started (trigger coil)
RE
(3)
(3) Reset, the timing relay is reset (reset coil)
FB output Data 3
Q1
(4)
(4) Switch contact
Table 6.191 Operand overview
Index
(hex)
Operand read write