Rockwell-automation 1760-DNET Pico DeviceNet Communications Module Use Manual de usuario Pagina 136

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 168
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 135
Publication 1760-UM003A-EN-P - September 2005
7-56 Pico GFX Control Commands
Sending of network data: PT01 – PT32
Table 6.176 Operand overview
Index
(hex)
Operand read write
00 Bit IO, Table 6.177 x
01 Mode/Parameter
02 Upper threshold value I1 x
c
(1)
(1) The value can only be written if it is assigned to a constant in the program.
03 Actual value of operating hours
counter
QV x
Table 6.177 Index 0 – Bit IO
Bit76543 2 1 0
FB input Data 1
RE
(1)
(1) Reset coil: Status 1 resets the counter actual value to zero.
EN
(2)
(2) Enable coil
FB output Data 3
Q1
(3)
(3) Status 1 if the setpoint was reached (greater than/equal to)
TIP
The data for index 2 and 3 is transferred as a 32-bit
value in Intel format (Data 1 – Low Byte to Data 4 –
High Byte).
Table 6.178 Telegram Structure
Byte Meaning Value (hex), sent by
Master Slave Master Slave
Attribute ID: Read 92
0 Response:
Read successful C2
Command rejected C0
0 1 Type 1F 1F
Vista de pagina 135
1 2 ... 131 132 133 134 135 136 137 138 139 140 141 ... 167 168

Comentarios a estos manuales

Sin comentarios