7-36 Pico GFX Control Commands
Comparator: CP01 – CP32
(1) The value can only be written if it is assigned to a constant in the program.
TIP
The data for index 2 to 5 is transferred as a 32-bit
value in Intel format (Data 1 – Low Byte to Data 4 –
High Byte).
Table 6.130 Index 0 – Bit IO
Bit76543 2 1 0
FB input Data 1 –––––
EN
(2)
(2) Counter enable
SE
(4)
(4) Transfer preset actual value on rising edge
RE
(6)
(6) Reset actual value to zero
FB output Data 3 ––––
ZE
(1)
(1) Zero: Status 1 if the value of the function block output QV (the counter status) equals zero
CY
(3)
(3) Carry: Status 1 if the value range is exceeded
FB
(5)
(5) Fall below: Status 1 if the actual value F lower setpoint
OF
(7)
(7) Overflow: Status 1 if the actual value f lower setpoint
Table 6.131 Telegram Structure
Byte Meaning Value (hex), sent by
Master Slave Master Slave
Attribute ID
Read 92
Write B2
0 Response:
Read successful C2
Write successful C1
Command rejected C0
0 1 Type 18 18
1 2 Instance 01 – 20 01 – 20
2 3 Index Table 6.132 Table 6.132