Specifications A-3
Table A.6 Tools and Cable Cross-Sections
Description Specification
Conductor cross-sections
Solid, minimum to maximum
0.2 to 4 mm
2
, 22 to 12 AWG
Conductor cross-sections
Flexible with ferrule, minimum to maximum
0.2 to 2.5 mm
2
, 22 to 12 AWG
Slot-head screwdriver, width 3.5 x 0.8 mm
Tightening torque 0.5 Nm
Table A.7 Power Supply
Description Specification
Rated Voltage Value 24V dc
Rated Voltage Range 20.4 ... 28.8V dc
Rated Voltage Residual Ripple <5 %
Rated Voltage Input Current at 24V dc,
typical
200 mA
Rated Voltage Dips, IEC/EN 61131-2 10 ms
Rated Voltage Power Loss at 24V dc typical 4.8 W
Table A.8 LED Displays
LED Color
Module Status LED MS Green/Red
Network Status LED NS Green/Red
Table A.9 DeviceNet
Description Specification
Device connection 5-pole socket
Electrical isolation Bus to power supply (simple)
Bus and power supply to basic unit (safety
isolation)
Function DeviceNetSlave
INTERFACE DeviceNet (CAN)
Bus protocol DeviceNet
Baud rate, automatic detection up to 500 kbps
Vista de pagina 150