Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 121
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Warning Status
This parameter warns the user of a
condition, without faulting.
Parameter Number 62
Access Rule GET
Data Type WORD
Group Basic Status
Units —
Minimum Value 0
Maximum Value 65535
Default Value 0
Bit
Warning
1514131211109876543210
——————————————— X Reserved
—————————————— X — Reserved
————————————— X —— Phase Loss
———————————— X ——— Reserved
——————————— X ———— Reserved
—————————— X ————— Control Power
————————— X —————— I/O Warning
———————— X ——————— Reserved
——————— X ———————— Phase Imbalance
—————— X ————————— A3 Power Loss
————— X —————————— Reserved
———— X ——————————— Reserved
——— X ———————————— Reserved
—— X ————————————— Hardware
X X —————————————— Reserved
Base Trip
The parameter determines the status
of the Base Module Trip Status.
Parameter Number 63
Access Rule GET
Data Type WORD
Group Basic Status
Units —
Minimum Value 0
Maximum Value 65535
Default Value 0