Rockwell Automation Publication 280E-UM001B-EN-P - July 2012 69
Product Commissioning Chapter 4
Figure 49 - Network Address Example
Valid IP address switch settings range from 001 to 254. When the switches are set
to a valid number, the adapters IP address will be 192.168.1.xxx (where xxx
represents the number set on the switches). The adapters subnet mask will be
255.255.255.0 and the gateway address is set to 0.0.0.0. A power cycle is required
for any new IP address to take effect.
Note: The upper three octets are fixed. DHCP or the embedded webserver must
be used to configure the IP address to a value other than 192.168.1.xxx.
If the switches are set to an invalid number (such as 000 or a value greater than
254), the adapter will check to see if DHCP is enabled. If DHCP is enabled, the
adapter requests an address from a DHCP server. If DHCP is not enabled, the
adapter will use the IP address (along with other TCP configurable parameters)
stored in non-volatile memory.
Figure 50 - Rotary Switch on Control Module
Refer to Figure 50, the ArmorStart is shipped with the control module rotary
switches set to a value of 99. DO NOT modify this setting. If these are changed
and the unit stops responding, the switches will need to be manually set to node
address 63 and power cycled.
X100
X10
X1
0
8
6
4
2
0
8
6
4
2
0
8
6
4
2
This example shows the
IP address set to 163.
Factory Setting 99