Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 145
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Pr Fault Enable
This parameter enables the Protection
Fault by setting the bit
to 1.
Parameter Number 24
Access Rule GET/SET
Data Type WORD
Group Starter Protection
Units
Minimum Value 64927
Maximum Value 65535
Default Value 64927
Bit
Function
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
——————————————— X Short Circuit
—————————————— X Overload
————————————— X —— Phase Loss
———————————— X ——— Ground Fault
——————————— X ———— Stall
————————— X ————— Control Power
————————— X —————— I/O Fault
———————— X ——————— Over Temperature
——————— X ———————— Over Current
—————— X ————————— A3 Power Loss
————— X —————————— Internal Comm
———— X ——————————— DC Bus Fault
——— X ———————————— EEprom
—— X ————————————— HW Fault
X —————————————— Restart Retries
X ——————————————— Misc. Fault
Pr Fault Reset
This parameter resets the Protection
Fault on a transition of
0 > 1.
Parameter Number 25
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0