Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 301
CIP Information Appendix B
The Fault text for this error is not return by the device, and is only reported as “Fault 45”.
DPI Alarm Object
CLASS CODE 0x0098
The following class attributes will be supported:
24 Power Loss Drive DC Bus Voltage remained below 85% of nominal bus voltage.
25 Under Voltage DC Bus Voltage fell below the minimum value.
26 Over Voltage DC Bus Voltage exceeded the maximum value.
27 MCB EEPROM This is a major fault which renders the ArmorStart inoperable.
28 Base EEPROM This is a major fault which renders the ArmorStart inoperable.
29 Drive EEPROM The drive EEPROM checksum checks have failed.
30 Wrong Base The ArmorStart controller is connected to the wrong base type.
31 Fan RMP The internal cooling fan is not running properly.
32 Power Unit A major failure has been detected in the drive power section.
33 Drive I/O Brd A failure has been detected in the drive control and I/O section.
34 Restart Retries Automatic fault reset and run retries exceeded.
35 Drive Aux In Flt The drive auxiliary input interlock is open inside the ArmorStart.
36 Analog Input (PF Fault Code 29)
37 Drv Param Reset Internal Drive Parameters (Parameters > 100) have been defaulted.
38 SCV Autotune The drive automatic tuning function was either aborted or failed.
39 Source Brake The source brake fuse has blown. Remove power and replace fuse.
40 Unknown Fault
41 DB1 Comm Communication with an internal DB1 board has been lost.
42 DB1 Fault A fault has been detected with the operation of the Dynamic Brake.
43 DB Switch Short The Dynamic Brake switch is shorted.
44 Fault 44
45
Incompatible COMM
Device
The Software revision of the Drive is not compatible with the ArmorStart.
Table 50 Bulletin 284E
Fault Code Fault Text Help Text
Attribute ID Access Rule Name Data Type Value
1 Get Class Revision UINT 1
2 Get Number of Instances UINT 1
3 Set Alarm Cmd Write USINT 0=NOP, 1=Clear Fault, 2=Clear Flt Queue
74 Get Alarm Instance Read UINT
The instance of the Fault Queue Entry containing information
about the Fault that tripped the Device.
6 Get Number of Recorded Faults UINT The number of Faults recorded in the Fault Queue.