Rockwell-automation 284E ArmorStart with EtherNet/IP - User Manual Manual de usuario Pagina 310

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 348
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 309
310 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Appendix C Using DeviceLogix
3. Refer to the tool bar at the top of the DeviceLogix editor window, click the
Move/Logical group and select the RSTD (Latch Reset). Move it to the
work space and click to drop it.
4. From the toolbar, Click on the “Bit Input” button and select In 0 from the
Hardware Boolean tree. This is the remote start button based on the
example I/O table.
5. Place the input to the left of the reset function. To drop the input on the
page, left click on the desired position.
6. Place the mouse cursor over the tip of In 0. The tip will turn green. Click
on the tip when it turns green.
Vista de pagina 309
1 2 ... 305 306 307 308 309 310 311 312 313 314 315 ... 347 348

Comentarios a estos manuales

Sin comentarios