Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 277
Appendix B
CIP Information
High Level Product
Description
The ArmorStart EtherNet/IP is an extension of the ArmorStart DeviceNet.
Three product types offered:
Product Codes and Name Strings
The following table lists the product codes and name strings that will be added
to the ArmorStart product family for EtherNet/IP.
CIP Explicit Connection
Behavior
The ArmorStart allows run, jog and user outputs to be driven by connected
explicit messages when no I/O connection exists, or when a I/O connection
exists in the idle state, a single EtherNet/IP Class 3 explicit connection will be
allowed to send “explicit control” messages via an “Active Explicit” connection.
An EtherNet/IP Class 3 explicit connection becomes the “explicit control”
Bulletin Number Distributed Starter Type
280E DOL
281E Reversing
284E Inverter
Product Code
(hex)
Product Code
(decimal) Identity Object Name String
0x91 145 ArmorStart Bulletin 280E 0.5…2.5 A 24V DC
0x92 146 ArmorStart Bulletin 280E 1.1…5.5 A 24V DC
0x93 147 ArmorStart Bulletin 280E 3.2…16 A 24V DC
0x9A 154 ArmorStart Bulletin 280E 0.3…1.5 A 24V DC
0xD1 209 ArmorStart Bulletin 281E 0.5…2.5 A 24V DC
0xD2 210 ArmorStart Bulletin 281E 1.1…5.5 A 24V DC
0xD3 211 ArmorStart Bulletin 281E 3.2…16 A 24V DC
0xDA 218 ArmorStart Bulletin 281E 0.3…1.5 A 24V DC
0x172 370 ArmorStart Bulletin 284E PF40 480V 0.5 Hp
0x174 372 ArmorStart Bulletin 284E PF40 480V 1 Hp
0x176 374 ArmorStart Bulletin 284E PF40 480V 2 Hp
0x177 375 ArmorStart Bulletin 284E PF40 480V 3 Hp
0x178 376 ArmorStart Bulletin 284E PF40 480V 5 Hp