280 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Appendix B CIP Information
Instance 1 of the Identity Object will contain the following attributes:
Instance 1 only
The following common services will be implemented for Instance 1. Service
requests to other instances are serviced through the bridge.
The Type 0 and 1 reset service types will reset the Control Module. The
EtherNet/IP module will perform the Type 0 or 1 reset on itself.
Attribute ID Access Rule Name Data Type Value
1 Get Vendor UINT 1
2 Get Device Type UINT 22
3 Get Product Code UINT Starter Rating specific
4 Get
Revision
Major Revision
Minor Revision
Structure of:
USINT
USINT
See table above.
5 Get Status WORD
Bit 0…0 = Not Owned; 1 = Owned by Master
Bit 2…0 = Factory Defaulted; 1 = Configured
Bit 8 - Minor Recoverable fault
Bit 9 - Minor Unrecoverable fault
Bit 10 - Major Recoverable fault
Bit 11 - Major Unrecoverable fault
6 Get Serial Number UDINT Unique number for each device
7 Get
Product Name
String Length
ASCII String
Structure of:
USINT
STRING
Product Code specific
8 Get State USINT Returns the value "3 = Operational"
9 Get
Configuration
Consistency Value
UINT "Module FRS"
102
Get Build Number UDINT Build number of EtherNet/IP Module firmware.
Service Code
Implemented for:
Service NameClass Instance
0x01 Yes Yes Get_Attributes_All
0x05 No Yes Reset
0x0E Yes Yes Get_Attributes_Single