282 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Appendix B CIP Information
I/O Assemblies
The following table summarizes the Assembly instances that are supported in the
ArmrorStart EtherNet/IP Product:
These assemblies are selectable on Inverter Type ArmorStart units only.
Instances 3 and 52 are required by the ODVA Motor Starter Profile. When used
as an EtherNet/IP Class 1 connection point, the I/O data attribute is simply
passed through the bridge.
Instance 3
This is the required output (consumed) assembly.
Instance 52
This is the required input (produced) assembly.
Instance Type Description
3 Consumed Required ODVA Consumed Instance
52 Produced Required ODVA Produced Instance
150 Produced Default Bulletin 280E/281E Produced Assembly
151
Produced Default Bulletin 284E Produced Assembly
162 Consumed Default Consumed Instance for DOL and Reversing Starters
166
Consumed Default Consumed Instance for Inverter type Starters
191 Consumed Empty assembly for Input Only I/O Connection
192 Consumed Empty assembly for Listen Only I/O Connection
Instance 3 ODVA Starter
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0——————Run Fwd
Instance 52 ODVA Starter
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
————RunningFault