152 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Drive I/O Configuration Group (Bulletin 284E only)
Drive Control
This parameter provides the status of
drive parameters.
Parameter Number 48
Access Rule GET
Data Type WORD
Group Drive I/O Config.
Units
Minimum Value 0
Maximum Value 4095
Default Value 0
Bit
Function
11109876543210
——————————— X Accel 1 En
—————————— X Accel 2 En
————————— X —— Decel 1 En
———————— X ——— Decel 2 En
——————— X ———— Freq Sel 0
—————— X ————— Freq Sel 1
————— X —————— Freq Sel 2
———— X ——————— Reserved
——— X ———————— Drv In 1
—— X ————————— Drv In 2
X —————————— Drv In 3
X ——————————— Drv In 4
DrvIn Pr FltState
This parameter, in conjunction with
Parameter 50 (DrvIn Pr FltValue),
defines how the Drive Digital
Inputs 1…4 will respond when a
protection trip occurs. When set to “1”,
Drive Digital Inputs 1…4 continue to
operate as command via the network.
When set to “0”, Drive Digital Inputs
1…4 will open or close as
determined by setting in Parameter
50.
0 = Go to PrFlt Value
1 = Ignore PrFlt
Parameter Number 49
Access Rule GET/SET
Data Type BOOL
Group Drive I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0