Rockwell Automation Publication 280E-UM001B-EN-P - July 2012 239
Chapter 11
Specifications for EtherNet/IP
Bulletin 280E/281E
Electrical Ratings UL/NEMA IEC
Power Circuit
Rated Operation Voltage 200…575V 200…575V
Rate Insulation Voltage 600V 600V
Rated Impulsed Voltage 6 kV 6 kV
Dielectric Withstand 2200V AC 2500V AC
Operating Frequency 50/60 Hz 50/60 Hz
Utilization Category N/A AC-3
Protection Against Shock N/A IP2X
Rated Operating Current Max.
280_-____-10A-* 1.2 A
280_-____-10B-* 2.5 A
280_-____-10C-* 5.5 A
280_-____-25D-* 16 A
Control Circuit
Rated Operation Voltage 24V DC (+10%, –15%) A2 (should be grounded at voltage source)
Rate Insulation Voltage 250V 250V
Rated Impulsed Voltage 4kV
Dielectric Withstand 1500V AC 2000V AC
Overvoltage Category III
Operating Frequency 50/60 Hz
Short Circuit
Protection
Short Circuit Protection Device
(SCPD) Performance Type 1
Current Rating Voltage 480Y/277V 480Y/480V 600Y/347V 600V
0.24…1.2 A
Sym. Amps rms
65 kA 65 kA 30 kA 30 kA0.5…2.5 A
1.1…5.5 A
3.2…16 A 30 kA 30 kA 30 kA 30 kA
SCPD List Size per NFPA 70 (NEC) or NFPA 79 for Group Motor Applications
See Contactor Life Load Curves on page 244