Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 155
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Output Current
Output Current present at T1, T2, T3.
Parameter Number 103
Access Rule GET
Data Type UINT
Group Drive Display
Units 0.01
Minimum Value 0.00
Maximum Value Drive rated amps x 2
Default Value Read Only
Output Voltage
Output Voltage present at T1, T2, T3.
Parameter Number 104
Related Parameters 131, 184, 188
Access Rule GET
Data Type UINT
Group Drive Display
Units 1V AC
Minimum Value 0
Maximum Value 480V
Default Value Read Only
DC Bus Voltage
Present DC Bus voltage level
Parameter Number 105
Access Rule GET
Data Type UINT
Group Drive Display
Units 1V DC
Minimum Value
Based on Drive Rating
Maximum Value
Default Value Read Only
Drive Status
Present operating condition of the
drive
Bit 0 = Running
Bit 1 = Forward
Bit 2 = Accelerating
Bit 3 = Decelerating
Parameter Number 106
Related Parameter 195
Access Rule GET
Data Type Byte
Group Drive Display
Units —
Minimum Value 0
Maximum Value 1
Default Value Read Only