164 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Drive Advanced Setup Group (Bulletin 284E only)
Reset To Defaults
Resets all parameter values to factory
defaults.
0 = Ready/Idle (Default)
1 = Factory Rset
Parameter Number 141
Access Rule GET/SET
Data Type BOOL
Group Drive Setup
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Motor OL Ret
Enables/disables the Motor overload
Retention function. When Enabled,
the value held in the motor overload
counter is saved at power-down and
restored at power-up. A change to this
parameter setting resets the counter.
0 = Disabled (Default)
1 = Enabled
Parameter Number 143
Access Rule GET/SET
Data Type BOOL
Group Drive Setup
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Digital In 1 SEL (151)
Digital In 2 SEL (152)
Digital In 3 SEL (153)
Digital In 4 SEL (154)
Selects the function for the digital
inputs.
Parameter Number 151…154
Related Parameters
112, 114, 138…140, 167, 168,
170…179, 240…247
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units
See Table20 for details.
Minimum Value
Maximum Value
Default Value
Stop drive before changing this
parameter.
Stop drive before changing this
parameter.